Civacon 8870

Overfill protection depot |

Artnr: 8870E

OPW CIVACON 8870 overfill protection and ground control. Designed for API bottom loading applications on single and multi-compartment tank cars at fuel depots.

8870 överfyllnadsskydd depå

Features and benefits

  • Automatic recognition of sensor technology
  • Supports up to 12 five-wire or 8 two-wire optical sensors
  • Self-check on startup; continuous self-monitoring
  • 1 separate user definable output relay. Overfill & Earth, Overfill, Earth, Smart Outlet.
  • Fail-safe redundant enabling output relays
  • LED individual status indicator
  • Graphic OLED screen
  • Time-stamped event logging
  • Vehicle data communication prepared
  • Sophisticated wireless multi-function and bypass key
  • Kill switch connection
  • Low temperature; useful in extreme environments and conditions as low as -45ºC
  • MODBUS communication available
  • Conforms to NEN EN13922, API RP1004 and VOC Directive 94/63/EC
  • Combine with OPW-Civacon Cane probe for peak loading applications on tankers or railcars.
  • SIL 1 standard, SIL 2 optional

Applications

  • Overfill protection and earthing control on e.g. fuel depots

Specifications

  • Power supply 85-264 V AC 50/60Hz
  • Nominal current consumption 4VA
  • Output relays 250V AC/DC 2AT
  • Communication; Optional RS485/422 data communication port
  • Operating temperature -45°C to +70°C
  • Response time < 200ms
  • Approvals ATEX / IECEx / QPS / PESO
  • Enclosure IP68 acc. to IEC 60529
  • Weight 7.3 kg
  • Dimensions 270x230x60 mm